[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
- 215 -
HWE14040
GB
7 Troub
le
sho
o
ting Using Erro
r
Cod
e
s
7-8-13
Error Code [6607] All Error Source Addresses
1. Error
code
definition
No ACK error
2. Error
definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. Cause, check method and remedy
(1) Troubleshooting problems for all units (A)
(2) Troubleshooting problems for all units (B)
(3) Troubleshooting problems for all units (C)
Cause
Check method and remedy
(1)
Disconnection or short circuit of the transmission line for
the outdoor unit on the terminal block for centralized con-
trol line connection (TB7)
1)
Check the causes of (1) - (4). If the cause is found,
correct it. If no cause is found, check 2).
(2)
When multiple outdoor units are connected and the pow-
er source of one of the outdoor units has been shut off.
2)
Check the LED displays for troubleshooting on oth-
er remote controllers whether an error occurs.
(3)
The male power supply connector of the outdoor unit is
not connected to the female power supply switch connec-
tor (CN40).
When an error is present
Check the causes of the error indicated by the
error codes listed in item (4) in the "Cause" col-
umn.
When no errors are present
Indoor unit circuit board failure
(4)
The male power supply connectors on 2 or more outdoor
units are connected to the female power supply switch
connector (CN40) for centralized control.
If an error occurs, after the unit runs normally once, the
following causes may be considered.
Total capacity error (7100)
Capacity code error (7101)
Error in the number of connected units (7102)
Address setting error (7105)
Cause
Check method and remedy
(1)
Total capacity error (7100)
1)
Check the LED display for troubleshooting on the
outdoor unit.
When an error is present
Check the causes of the error indicated by the
error codes listed in items (1) through (4) in the
"Cause" column.
When no errors are present
Check the causes of the error indicated by the
error codes listed in items (5) through (7) in the
"Cause" column.
(2)
Capacity code error (7101)
(3)
Error in the number of connected units (7102)
(4)
Address setting error (7105)
(5)
Disconnection or short circuit of the transmission line for
the outdoor unit on the terminal block for centralized con-
trol line connection (TB7)
(6)
Turn off the power source of the outdoor unit
(7)
Malfunction of electrical system for the outdoor unit
Cause
Check method and remedy
(1)
When the power supply unit for transmission lines is used
and the male power supply connector is connected to the
female power supply switch connector (CN40) for the
transmission line for centralized control
Check the causes of the error indicated by the
error codes listed in items (1) through (3) in the
"Cause" column.
(2)
Disconnection or shutdown of the power source of the
power supply unit for transmission line
(3)
System controller (MELANS) malfunction
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......