[6-9 Evaluating and Adjusting Refrigerant Charge ]
- 134 -
HWE14040
GB
(2) Example: PUHY-P350YKB-A1
(3) Sample calculation
A
B
C
D
e
a
b
c
d
Indoor 1: P125
40 m
10 m
2: P100
10 m
5 m
3: P40
15 m
10 m
4: P32
10 m
10 m
5: P63
10 m
The total length of liquid pipe of each size is as follows:
ø12.7: A + e = 40 + 10 = 50 m
A: ø12.7
a: ø9.52
b: ø9.52
c: ø6.35
d: ø9.52
e: ø12.7
B: ø9.52
C: ø9.52
D: ø9.52
ø9.52: B + C + D + a + b + d = 10 + 15 + 10 + 10 + 5 + 10 = 60 m
ø6.35: c = 10 = 10 m
P40
P100
P125
P32
P63
=
+
+
+
+
+ 3.5
+
+
+
+
+ 3.5
+ 0
+ 0
(kg)
0 (m) x 0.26 (kg/m)
Additional
refrigerant charge
=
0 0
50
x 0.11 60
x 0.054
10
x 0.021
= 12.5 (12.45) kg
Total length of liquid
x 0.26 (kg/m)
0 (m) x 0.18 (kg/m)
Total length of liquid
x 0.18 (kg/m)
50 (m) x 0.11 (kg/m)
Total length of liquid
x 0.11 (kg/m)
60 (m) x 0.054 (kg/m)
Total length of liquid
x 0.054 (kg/m)
10 (m) x 0.021 (kg/m)
Total length of liquid
x 0.021 (kg/m)
CAUTION
Charge liquid refrigerant (as opposed to gaseous refrigerant) into the system.
If gaseous refrigerant is charged into the system, the composition of the refrigerant in the cylinder will change and may
result in performance loss.
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......