[3-3 Functions of the Major Components of Outdoor Unit ]
- 63 -
HWE14040
GB
3
Major
Compo
n
ent
s
, The
ir Fu
nct
io
n
s and
Ref
riger
ant
Circ
uit
s
Sole-
noid
valve
SV1a
Discharge-
suction
bypass
1) High/low pressure bypass at
start-up and stopping, and
capacity control during low-
load operation
2) High-pressure-rise preven-
tion
AC220-240V
Open while being powered/
closed while not being pow-
ered
Continuity check
with a tester
SV5b
Heat
exchanger
capacity con-
trol
P450,
P500
models
only
Controls outdoor unit heat ex-
changer capacity
AC220-240V
Closed while being powered/
open while not being powered
SV9
High-pressure-rise prevention
Open while being powered/
closed while not being pow-
ered
SV10
Continuous heating cycle mode
Open while being powered/
closed while not being pow-
ered
SV11
Continuous heating cycle mode
Open while being powered/
closed while not being pow-
ered
Linear
expan-
sion
valve
LEV1
(SC control)
Adjusts the amount of bypass flow
from the liquid pipe on the outdoor
unit during cooling
DC12V
Opening of a valve driven by a
stepping motor 0-480 pulses
(direct driven type)
Same as indoor
LEV
The resistance val-
ue differs from that
of the indoor LEV.
Refer to the follow-
ing page(s). [8-8
Troubleshooting
LEV Prob-
lems](page 258)
LEV2a
(Refrigerant
flow adjust-
ment)
Adjusts refrigerant flow during
heating
Cut off the refrigerant flow during
continuous heating cycle
DC12V
Opening of a valve driven by a
stepping motor 2100 pulses
(Max. 3000 pulses)
Refer to the section
"Continuity Test
with a Tester".
Continuity between
white and orange.
Continuity between
yellow, red, and
blue.
LEV2b
(Refrigerant
flow adjust-
ment)
4-way
valve
21S4a
Changeover between heating and
cooling
AC220-240V
Dead: cooling cycle
Live: heating cycle
Continuity check
with a tester
21S4b
1) Changeover between heating
and cooling
2) Controls outdoor unit heat ex-
changer capacity
AC220-240V
Dead: cooling cycle
Outdoor unit heat exchanger
capacity at 100%
Live: heating cycle
Outdoor unit heat exchanger
capacity at 25%, 50%
or heating cycle
21S4c P450,
P500
models
only
Fan
motor
FAN motor
1,2
FAN mo-
tor 2 is
only on
the P450,
P500
models.
Regulates the heat exchanger ca-
pacity by adjusting the operating
frequency and operating the pro-
peller fan based on the operating
pressure.
AC380-400V, 920W
*The P200-P400 models and
the P450 model are equipped
with different types of fan mo-
tors.
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check method
Yellow
White
Orange
red
Blue
M
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......