[5-1 Dipswitch Functions and Factory Settings ]
- 85 -
HWE14040
GB
5 Cont
rol
5 Control
5-1
Dipswitch Functions and Factory Settings
5-1-1
Outdoor Unit Switch Functions and Factory Settings
(1) Control board
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on OC needs to be set for the setting to be effective.
B: The switches on both the OC and OS need to be set to the same seeing for the setting to be effective.
C: The switches on both the OC and OS need to be set.
3) When set to the performance-priority mode, the low-noise mode will be terminated, and the units will operate in the normal
mode.
Cooling: Ambient temperature or the high pressure is high.
Heating: When the outside air temperature is low or when the low pressure is low. Refer to the following page(s). [2-4-7 Var-
ious Control Methods Using the Signal Input/Output Connector on Outdoor Unit](page 25)
4) Operation noise is reduced by controlling the compressor frequencies and the rotation speed of the outdoor unit fans.
CN3D needs to be set. Refer to the following page(s). [2-4-7 Various Control Methods Using the Signal Input/Output Connec-
tor on Outdoor Unit](page 25)
5) Operation noise is reduced by limiting the frequency of the compressor and rotation speed of the outdoor unit fan.
Switch
Function
Function according to switch setting
Switch setting timing
Units that require
switch setting
(Note 2)
OFF
ON
SWU
1-2
Unit address setting
Set to 00 or 51-100 with the dial switch
Before power on
C
SW5
1
Centralized control
switch
Without connec-
tion to the central-
ized controller
With connection to
the centralized con-
troller
Before power on
B
2
Deletion of connection
information
Normal control
Deletion
Before power on
A
3
-
Preset before shipment
-
4
-
-
5
-
-
6
-
-
7
-
-
8
-
-
SW6
1
-
-
-
-
-
2
COP priority setting (at
low outside tempera-
ture)
Heating capacity
priority control
mode
Heating COP priori-
ty mode
Before power on
A
3
-
-
-
-
-
4
Model setting (outdoor
unit/high static pres-
sure setting)
Normal static pres-
sure
High static pres-
sure
Before power on
C
5
Model setting (outdoor
unit/high static pres-
sure setting)
High (60 Pa)
High (30 Pa)
Before power on
C
6
-
-
-
-
-
7
Performance-priority/
low-noise mode setting
Performance-pri-
ority mode (Note 3)
Quiet-priority mode
(Note 5)
Anytime after power
on
A
8
Low-noise mode/step
demand switching
Low-noise mode
(Note 4)
Step demand mode Before power on
C
9
-
-
-
-
-
10
Self-diagnosis monitor
display / SW4 function
setting mode switching
Self-diagnosis
monitor display
SW4 function set-
ting mode
Anytime after power
on
C
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......