[5-2 Outdoor Unit Control ]
- 102 -
HWE14040
GB
5-2-14
Emergency Operation Mode
1. Problems
with the outdoor unit
Emergency operation mode is a mode in which outdoor units that are operating normally take over the operation of the out-
door units that are experiencing problems. (P400-P900YSKB models go into an emergency operation mode when one out-
door unit is in trouble, and P950-P1350YSKB models go into an emergency operation mode when one or two outdoor units
are in trouble.)
This mode can be started by performing an error reset via the remote controller.
(1) Starting the emergency operation
1) When an error occurs, the error source and the error code will be displayed on the display on the remote controller.
2) The error is reset using the remote controller.
3) If an error code appears that permits an emergency operation in step 1) above, (See the table below.), the retry operation
starts.
4) If the same error is detected during the retry operation (step 3 above), an emergency operation can be started by resetting
the error via the remote controller.
Error codes that permit an emergency operation (Applicable to both OC and OS)
Emergency operation pattern (2 outdoor units)
Trouble source
Error codes that permit an
emergency operation
Error code description
Compressor
Fan motor
Inverter
0403
Serial communication error
4220,4225,4226
Bus voltage drop
4230,4235
Heatsink overheat protection
4240,4245
Overload protection
4250,4255,4256
Overcurrent relay trip
5110
Heatsink temperature sensor failure (THHS)
5120
DCL temperature sensor circuit fault
5301
Current sensor/circuit failure
5305,5306
Position error
Thermistor
TH2
5102
Subcool heat exchanger bypass outlet temperature sensor failure
TH3
5103
Pipe temperature sensor failure
TH4
5104
Discharge temperature sensor failure
TH5
5105
Accumulator inlet temperature sensor failure
TH6
5106
Subcool heat exchanger liquid outlet sensor failure
TH7
5107
Outside air temperature sensor failure
TH9
5109
Continuous heating temperature sensor fault
TH11
5111
Continuous heating temperature sensor fault
Power
4102
Open phase
4115
Power supply sync signal abnormality
OC
OC failure
pattern
Trouble
Normal
Permitted Permitted
Permitted Permitted
60%
Cooling
Heating
Normal
Trouble
OS failure
pattern
OS
Emergency
operation
Maximum total capacity
of indoor units (Note 1)
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......