[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
- 192 -
HWE14040
GB
7-6-16
Error Code [4230] Detail Code 126
1. Error
code
definition
DCL temperature fault (Detail code 126)(outdoor unit)
2. Error
definition and error detection method
When DCL temperature that equals or exceeds 170˚C is detected (applicable to INV30YC only)
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems](page 264)
Cause
Check method and remedy
(1)
Fan inverter board fault
Refer to the following page(s). [8-9-8 Checking the Fan Board Error Detection Circuit
at No Load](page 269)
Refer to the following page(s). [8-9-9 Checking the Fan Inverter for Damage at No
Load](page 270)
Refer to the following page(s). [8-9-10 Checking the Fan Inverter for Damage with
Load](page 271)
(2)
Outdoor unit fan fault
Check the outdoor unit fan for proper operation.
If there is a problem with fan operation, check the fan motor. Refer to the following
page(s). [8-9-7 Checking the Fan Motor for Ground Fault and Coil Resistance Prob-
lems](page 269)
(3)
DCL temperature sen-
sor connector contact
failure
Check the connector (CNTH) on the inverter board for proper connection.
(4)
DCL error
If the problem persists after restart, replace the DCL.
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......