[7-3 Error Code Definitions and Solutions: Codes [1000 - 1999] ]
- 171 -
HWE14040
GB
7 Troub
le
sho
o
ting Using Erro
r
Cod
e
s
7-3
Error Code Definitions and Solutions: Codes [1000 - 1999]
7-3-1
Error Code [1102]
1. Error
code
definition
Discharge temperature fault
2. Error
definition and error detection method
1) If the discharge temperature of 120 °C [248°F] or more is detected during the above operation (the first detection), the outdoor
unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically.
2) If the discharge temperature of 120° C [248°F] or more is detected again (the second detection) within 30 minutes after the
second stop of the outdoor unit described above, the mode will be changed to 3 - minute restart mode, then the outdoor unit
will restart in 3 minutes.
3) If the discharge temperature of 120°C [248°F] or more is detected (the 30th detection) within 30 minutes after the stop of the
outdoor unit described above (regardless of the first or the 29th stop), the outdoor unit will make an error stop, and the error
code "1102" will be displayed.
4) If the discharge temperature of 120°C [248°F] or more is detected more than 30 minutes after the previous stop of the outdoor
unit, the detection is regarded as the first detection, and the operation described in step 1 above will start.
5) For 30 minutes after the stop (the first stop or the second stop) of the outdoor unit, preliminary errors will be displayed on the
LED display.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Gas leak, gas shortage
Refer to the following page(s).[6-9 Evaluating and Adjusting
Refrigerant Charge](page 131)
(2)
Overload operation
Check operating conditions and operation status of indoor/
outdoor units.
(3)
LEV failure on the indoor unit
Perform a cooling or heating operation to check the opera-
tion.
Cooling: Indoor unit LEV, LEV1, LEV2
Heating: Indoor unit LEV, LEV2
Refer to the following page(s). [8-8 Troubleshooting LEV
Problems](page 258)
(4)
Outdoor unit LEV1 actuation failure
Outdoor unit LEV2 actuation failure
(5)
Closed refrigerant service valve
Confirm that the refrigerant service valve is fully open.
(6)
Outdoor fan (including fan parts) failure, mo-
tor failure, or fan controller malfunction
Rise in discharge temp. by low pressure
drawing for (3) - (6).
Check the fan on the outdoor unit.
Refer to the following page(s). [8-7 Troubleshooting Outdoor
Unit Fan Problems](page 257)
(7)
Gas leak between low and high pressures
(4-way valve failure, Compressor failure, So-
lenoid valve (SV1a) failure)
Perform a cooling or heating operation and check the opera-
tion.
(8)
Thermistor failure
(TH4)
Refer to the following page(s).
(9)
Input circuit failure on the controller board
thermistor
Check the inlet air temperature on the LED monitor.
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......