[6-5 Making Interlock Settings from an MA Remote Controller ]
- 125 -
HWE14040
GB
6
T
est
Ru
n
<1. Registration procedure>
Set the address of the indoor unit to be interlocked with the LOSSNAY unit using the
and
buttons. (01 to 50)
After setting, press the
button and set the Lossnay address you want to register by
operating the
and
buttons. (01~50)
Press the
button, and register the set indoor unit address and LOSSNAY address.
- Registration end display
The indoor unit address and “IC” and LOSSNAY address and “LC” are alternately displayed.
- Registration error display
If the address is not registered correctly, the indoor unit address and [
], and the registered
LOSSNAY and [
] are alternately displayed.
Cannot be registered because the registered indoor unit or LOSSNAY does not exist.
Cannot be registered because another LOSSNAY was registered at the registered indoor unit.
..
.
.
.
Indoor unit address
LOSSNAY or OA processing unit address
ON
OFF
5
6
7