[7-3 Error Code Definitions and Solutions: Codes [1000 - 1999] ]
- 174 -
HWE14040
GB
7-3-4
Error Code [1302] (at startup)
1. Error
code
definition
High pressure fault 2 (Outdoor unit)
2. Error
definition and error detection method
If the pressure of 0.098MPa [14psi] or lower is registered on the pressure sensor immediately before start-up, it will trigger an
abnormal stop, and error code "1302" will be displayed.
3. Cause, check method and remedy
7-3-5
Error Code [1500]
1. Error
code
definition
Refrigerant overcharge
2. Error
definition and error detection method
An error can be detected by the discharge temperature superheat.
1) If the formula "TdSH
10°C [18°F]" is satisfied during operation (first detection), the outdoor unit stops, goes into the 3-minute
restart mode, and starts up in three minutes.
2) If the formula "TdSH
10°C [18°F]" is satisfied again within 30 minutes of the fifth stoppage of the outdoor unit (sixth detec-
tion), the unit comes to an abnormal stop, and the error code "1500" appears.
3) If the formula "TdSH
10°C [18°F]" is satisfied 30 minutes or more after the first stoppage of the outdoor unit, the same se-
quence as Item "1 above (first detection) is followed.
4) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Inner pressure drop due to a leakage.
Refer to the following page(s). [8-5-1 Comparing the
High-Pressure Sensor Measurement and Gauge
Pressure](page 253)
(2)
Pressure sensor failure
(3)
Shorted-circuited pressure sensor cable due to torn
outer rubber
(4)
A pin on the male connector on the pressure sensor
is missing or contact failure
(5)
Disconnected pressure sensor cable
(6)
Failure of the pressure sensor input circuit on the
controller board
Cause
Check method and remedy
(1)
Overcharged refrigerant
Refer to the following page(s). [6-9 Evaluating and Adjust-
ing Refrigerant Charge](page 131)
(2)
Thermistor input circuit failure on the control board
Check the temperature and pressure readings on the sen-
sor that are displayed on the LED monitor.
(3)
Faulty mounting of thermistor (TH4)
Check the temperature and pressure readings on the
thermistor that are displayed on the LED monitor.
(4)
Outdoor unit LEV2 actuation failure -> Heating
Refer to the following page(s). [8-8 Troubleshooting LEV
Problems](page 258)
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......