[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
- 212 -
HWE14040
GB
7-8-10
Error Code [6607] Error Source Address = LOSSNAY (LC)
1. Error
code
definition
No ACK error
2. Error
definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. Cause, check method and remedy
(1) Troubleshooting problems for LOSSNAY units
Error display
ME remote controller (RC), MA remote controller (MA)
Types of refrigerant systems
Single refrigerant system
Grouped operation of multiple
refrigerant systems
Troubleshooting problems for
LOSSNAY units
Troubleshooting problems for
LOSSNAY units
&
Troubleshooting problems for
all units (A)
Cause
Check method and remedy
(1)
Incidental cause
1)
Turn off the power source of LOSSNAY and turn it
on again.
(2)
The power source of LOSSNAY has been shut off.
2)
If the error is accidental, it will run normally.
If not, check the causes (2) - (6).
(3)
When the address of LOSSNAY is changed in the middle
of the operation
(4)
Faulty or disconnected transmission wiring of LOSSNAY
(5)
Disconnected connector (CN1) on LOSSNAY
(6)
Controller failure of LOSSNAY
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......