[2-5 Demand Control Overview ]
- 29 -
HWE14040
GB
2 Rest
rict
io
ns
2) When SW6-8 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND)
(*3)
*3. Input the order to CN3D on the outdoor unit whose SW6-8 is set to ON.
3) When SW6-8 on the two outdoor units in one refrigerant circuit system is set to ON (8 levels of on-DEMAND)
(*4, *5)
*4. Input the order to CN3D on the outdoor unit whose SW6-8 is set to ON.
*5. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW6-8 is set to ON.
4) When SW6-8 on the all outdoor units in one refrigerant circuit system is set to ON (12 levels of on-DEMAND)
(*4)
*3. Input the order to CN3D on the outdoor unit whose SW6-8 is set to ON.
*4. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW6-8 is set to ON.
CN3D 1-2P
CN3D 1-3P
Open
Short-circuit
Open
100% (No DEMAND)
75%
Short-circuit
0% (Compressor OFF)
50%
8 levels of on-DEMAND
No.2 CN3D
1-2P
Open
Short-circuit
No.1 CN3D
1-2P
1-3P
Open
Short-circuit
Open
Short-circuit
Open
Open
100%
50%
88%
75%
Short-circuit
50%
0%
38%
25%
Short-circuit
Open
88%
38%
75%
63%
Short-circuit
75%
25%
63%
50%
12 levels
of on-DE-
MAND
No.2 CN3D
1-2P
Open
1-3P
Open
Short-circuit
No.3 CN3D
1-2P
Open
Short-circuit
Open
Short-circuit
No.1
CN3D
1-2P
1-3P
Open
Short-
circuit
Open
Short-
circuit
Open
Short-
circuit
Open
Short-
circuit
Open
Open
100%
67%
92%
84%
67%
34%
59%
50%
Short-
circuit
67%
34%
59%
50%
34%
0%
25%
17%
Short-circuit
Open
92%
59%
84%
75%
59%
25%
50%
42%
Short-
circuit
84%
50%
75%
67%
50%
17%
42%
34%
12 levels
of on-DE-
MAND
No.2 CN3D
1-2P
Short-circuit
1-3P
Open
Short-circuit
No.3 CN3D
1-2P
Open
Short-circuit
Open
Short-circuit
No.1
CN3D
1-2P
1-3P
Open
Short-
circuit
Open
Short-
circuit
Open
Short-
circuit
Open
Short-
circuit
Open
Open
92%
59%
84%
75%
84%
50%
75%
67%
Short-
circuit
59%
25%
50%
42%
50%
17%
42%
34%
Short-circuit
Open
84%
50%
75%
67%
75%
42%
67%
59%
Short-
circuit
75%
42%
67%
59%
67%
34%
59%
50%
If the step listed as the wrong example above is taken, thermo may go off.
The percentage of the demand listed in the table above is an approximate value based on the
compressor volume and does not necessarily correspond with the capacity.
When this function is enabled, the night mode cannot be enabled.
(Wrong)
(Correct)
100%
100%
0%
75%
50%
50%
Demand control
steps
Note the following steps to be taken when using the STEP DEMAND
(Example) When switching from 100% to 50%
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......