[8-3 Refrigerant Control Problems ]
- 249 -
HWE14040
GB
8 Trou
ble
s
ho
oting
Bas
e
d on Obse
rved
Sy
mpto
ms
8-3-3
Outdoor Units Stop at Irregular Times.
1. Phenomena
Outdoor unit stops at times during operation.
2. Cause, check method and remedy
Cause
Check method and remedy
The first stop is not considered as an error, as the
unit turns to anti-restart mode for 3 minutes as a pre-
liminary error.
(1)
Check the mode operated in the past by displaying
preliminary error history on LED display with SW4.
Error mode
(2)
Reoperate the unit to find the mode that stops the
unit by displaying preliminary error history on LED
display with SW4.
Refer to the reference page for each error mode.
1)
Abnormal high pressure
2)
Abnormal discharge air temperature
3)
Heatsink thermistor failure
*Display the indoor piping temperature table with
SW4 to check whether the freeze proof operation
runs properly, and check the temperature.
4)
Thermistor failure
Refer to the following page(s).9 LED Status Indica-
tors on the Outdoor Unit Circuit Board(page 289)
5)
Pressure sensor failure
6)
Over-current break
7)
Refrigerant overcharge
Note1: Frost prevention tripping only under cooling mode
may be considered in addition to the above. (Freeze
protection is detected by one or all indoor units.)
Note2: Even the second stop is not considered as an error
when some specified errors occur. (eg. The third
stop is considered as an error when the thermistor
error occurs.)
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......