[8-9 Troubleshooting Inverter Problems ]
- 268 -
HWE14040
GB
<INV30YC>
3)
A BUS circuit error occurs immediately
after compressor startup.
Error code : 4220
Detail code : 124
a.
Check that 12 VDC is supplied to
the relay at startup (Check that
LED5 lights up.)Between pins 1 (+)
and 2 (-) on the CNRY connector
b.
Replace the inverter board if no
problems were found with item a.
4)
An overcurrent error occurs during oper-
ation.
Error code : 4250
Detail code : 121,122
[8-9-6 Checking the Converter for
Damage during Compressor Oper-
ation](page 269)
5)
An overcurrent error occurs immediately
after compressor startup.
Error code : 4250
Detail code :101,106,107,128
a.
Check for refrigerant flooding.
→
When the problem persists after
compressor startup was repeated
several times, go to "d" after a cer-
tain time after energizing the com-
pressor or the heater.
If normal operation is restored,
check the belt heater for problems.
b.
Check that there is a pressure dif-
ference between high and low
pressures after compressor start-
up.
→
Check the high pressure with
LED monitor for changes.
Replace the compressor if there is
no pressure difference. (the com-
pressor may be locked.)
c.
Check for interphase voltage im-
balance.
d.
Replace the INV board if no prob-
lems were found with the items a or
c.
e.
If the problem persists after replac-
ing the inverter board,[8-9-3
Checking the Compressor for
Ground Fault and Coil Resistance
Problems](page 266)
6)
An overvoltage error occurs during oper-
ation.
Error code : 4220
Detail code :109,110,112
[8-9-6 Checking the Converter for
Damage during Compressor Oper-
ation](page 269)
7)
No problems were found with items 1)
through 6).
Normal[8-9-6 Checking the Con-
verter for Damage during Com-
pressor Operation](page 269)
Items to be checked
Phenomena
Remedy
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......