Error Code [4115]
1. Error
code
definition
Power supply signal sync error
2. Error
definition and error detection method
The frequency cannot be determined when the power is switched on.
3. Cause, check method and remedy
7-6-5
Error Code [4116]
1. Error
code
definition
RPM error/Motor error
2. Error
definition and error detection method
LOSSNAY
The motor keep running even if the power is OFF.
The thermal overload relay is ON. (Only for the three-phase model)
Indoor unit
If detected less than 180rpm or more than 2000rpm, the indoor unit will restart and keep running for 3 minutes.If detected
again, the display will appear.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Power supply error
Check the voltage of the power supply terminal
block (TB1).
(2)
Noise filter problem
Coil problem
Circuit board failure
Check the coil connections.
Check for coil burnout.
Confirm that the voltage at the CN3 connector is
198 V or above.
(3)
Faulty wiring
Check fuse F01 on the control board.
(4)
Wiring failure
Between noise filter CN3 and noise filter CN2 and con-
trol board CNAC
Confirm that the voltage at the control board con-
nector CNAC is 198 V or above.
(5)
Control board failure
If none of the items described above is applicable,
and if the trouble reappears even after the power is
switched on again, replace the control board.
Cause
Check method and remedy
(1)
Board failure
Replace the board.
(2)
Motor malfunction
Check for the motor and the solenoid switch.
(3)
Solenoid switch malfunction
Summary of Contents for PUHY-P1000
Page 1: ......
Page 11: ... 2 HWE14040 GB ...
Page 27: ... 18 HWE14040 GB ...
Page 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Page 61: ... 52 HWE14040 GB ...
Page 75: ... 66 HWE14040 GB ...
Page 93: ... 84 HWE14040 GB ...
Page 121: ... 112 HWE14040 GB ...
Page 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Page 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Page 297: ... 288 HWE14040 GB ...
Page 334: ......