[8-9 Troubleshooting Inverter Problems ]
- 274 -
HWE14040
GB
INV board external diagram
<INV20Y>
Judgment value (reference)
Black ( + )
SC-P1
FT-N
SC-L1
SC-L2
SC-L3
Red (-)
SC-P1
-
-
5 - 200
Ω
5 - 200
Ω
5 - 200
Ω
FT-N
-
-
∞
∞
∞
SC-L1
∞
5 - 200
Ω
-
-
-
SC-L2
∞
5 - 200
Ω
-
-
-
SC-L3
∞
5 - 200
Ω
-
-
-
Black ( + )
SC-P2
FT-N
SC-U
SC-V
SC-W
Red (-)
SC-P2
-
-
5 - 200
Ω
5 - 200
Ω
5 - 200
Ω
FT-N
-
-
∞
∞
∞
SC-U
∞
5 - 200
Ω
-
-
-
SC-V
∞
5 - 200
Ω
-
-
-
SC-W
∞
5 - 200
Ω
-
-
-
SC-U
SC-W
SC-V
FT-N
SC-P1
SC-P2
SC-L1
SC-L2
SC-L3
Summary of Contents for PUHY-P1000