[5-1 Dipswitch Functions and Factory Settings ]
4
-
chapter 5
HWE18240_GB
5 Control
(2) Additional dipswitch settings at time of shipment
Switch
Function
Function according to switch setting
Switch setting timing
Units that
require
switch
setting
(Note 2)
OFF (LED3 Unlit)
ON (LED3 Lit)
SW4
SW6-10:
OFF
1-10
1:ON, 0:OFF
Self-diagnosis/operation
monitor
Anytime after power on
C
SW4
1-10
[0:OFF,
1:ON]
(Note 1)
SW6-10:ON
No.769
1000000011
Test run mode: ON/OFF
Stops all ICs
Sends a test-run sig-
nal to all IC
Anytime after power on
A
No.817
1000110011
Starts up drive recorder
Enabled
Disabled
Anytime after power on
A
No.818
0100110011
Data collection during an
error
Disabled
Enabled
Anytime after power on
A
No.832
0000001011
Cumulative compressor
operation time deletion
Retained
Cleared
Any time after being energized (When
changed from OFF to ON)
C
No.848
0000101011
Continuous heating cycle
function
Disabled
Enabled
After being energized and while the com-
pressor is stopped
B
No.891
1101111011
Smooth auto-shift startup
mode during startup of
heating operation
Disabled
Enabled
After being energized and while the com-
pressor is stopped
A
No.896
0000000111
Clearance of error
history
OC
Retained (IC/OC)
Deleted (IC/OC)
Anytime after power on (OFF
ĺ
ON)
C
OS
Retained (OS)
Deleted (OS)
No.897
1000000111
High sensible heat opera-
tion setting
Depends on the combined setting with No.
900 (Note 4)
(Factory setting: OFF)
After being energized and while the com-
pressor is stopped
A
No.900
0010000111
High sensible heat opera-
tion setting
Depends on the combined setting with No.
897 (Note 4)
(Factory setting: OFF)
After being energized and while the com-
pressor is stopped
A
No.912
0000100111
Pump down function
Normal control
Pump down opera-
tion
After being energized and while the com-
pressor is stopped
A
No.913
1000100111
Forced defrost (Note 3)
Normal control
Forced defrost starts
Anytime after power on
10 minutes after the completion of de-
frost operation (OFF
ĺ
ON) or 10 minutes
after compressor start-up (OFF
ĺ
ON)
D
No.915
1100100111
Defrost start temperature
(Note 3)
HP72 - HP120:
-11°C [12°F]
-8°C [18°F]
Anytime after power on
B
No.916
0010100111
Defrost end temperature
(Note 3)
HP72 - HP120:
7°C [45°F]
5°C [41°F]
Anytime after power on
B
No.918
0110100111
Changes the defrost timer
setting (Note 3)
50 minutes
90 minutes
Anytime after power on (OFF
ĺ
ON)
B
No.921
1001100111
Temperature/pressure unit
selection
°C/kgf/cm
2
°F/psi
Anytime after power on
C
No.922
0101100111
Refrigerant amount adjust-
ment
Normal control
Refrigerant amount
adjust mode
Anytime after power on (except during
initial startup/becomes ineffective 90
minutes after compressor started up.)
A
No.932
0010010111
Heating backup
Disabled
Enabled
Anytime after power on
A
No.933
1010010111
Snow sensor setting
Effective only when
TH7
5 is true or the
snow sensor contact
input is on.
Effective when TH7
5 is true
Anytime after power on
C
No.934
0110010111
Snow sensor setting
Continuous fan op-
eration (FAN=50%)
Intermittent fan op-
eration (The fan op-
erates in the cycle of
being in operation at
100% capacity for 5
minutes and then
stops and remains
stopped for 30 min-
utes.)
Anytime after power on
C
No.964
0010001111
Target evaporation tem-
perature setting
Depends on the setting combination with No.
982 (Note 5)
(Factory setting: OFF)
Anytime after power on
A
No.968
0001001111
Target condensation tem-
perature setting
(Tcm max=53°C [126°F])
Disabled
Enabled
Anytime after power on
A
No.972
0011001111
Automatic cooling/heating
mode (IC with the smallest
address)
Normal control
Automatic cooling/
heating mode
Before power on (After configuring the
setting, perform a power reset.)
A
No.974
0111001111
Panel heater output
Enabled
Disabled
After being energized and while the com-
pressor is stopped
D
No.982
0110101111
Target evaporation tem-
perature setting
Depends on the setting combination with No.
964 (Note 5)
(Factory setting: OFF)
Anytime after power on
A
No.988
0011101111
Refrigerant recovery/Evac-
uation (LEV2, LEV1, SV2
open)
Disabled
Enabled
After being energized and when units are
stopped
C
No.997
1010011111
Multiple-stage low-noise
setting
See note 8 below.
(Factory setting: OFF)
After power on and while the compressor
is stopped
A
No.1006
0111011111
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......