[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
HWE18240_GB
chapter 7 -
37
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-6-27
Error Code [4260]
1. Error code definition
Heatsink overheat protection at startup
2. Error definition and error detection method
When heatsink temperature (THHS) remains at or above TOH for 10 minutes or longer after inverter startup
3. Cause, check method and remedy
Same as 4230 error
models
TOH
INV42Y, INV38
100
Û
C