[2-10 Restrictions on Refrigerant Pipes ]
HWE18240_GB
chapter 2 -
29
2 Restrictions
2-10-2
Restrictions on Refrigerant Pipe Size
(1) Diameter of the refrigerant pipe between the outdoor unit and the first branch (outdoor unit pipe
size)
(2) Size of the refrigerant pipe between the first branch and the indoor unit (indoor unit pipe size)
Outdoor unit set name
(total capacity)
Liquid pipe size (mm) [inch]
Gas pipe size (mm) [inch]
72 model
ø9.52 [3/8"]
ø22.2 [7/8"]
96 model
ø9.52 [3/8"]
*1
*1. Use ø12.7 [1/2"] pipes if the piping length to the farthest indoor unit exceeds 90 m [295 ft].
ø22.2 [7/8"]
120 model
ø9.52 [3/8"]
*2
*2. Use ø12.7 [1/2"] pipes if the piping length to the farthest indoor unit exceeds 40 m [131 ft].
ø28.58 [1-1/8"]
144 model
ø12.7 [1/2"]
ø28.58 [1-1/8"]
192 model
ø15.88 [5/8"]
ø28.58 [1-1/8"]
240 model
ø15.88 [5/8"]
ø28.58 [1-1/8"]
model
Pipe diameter (mm) [inch]
05 - 15 models
Liquid pipe
ø6.35 [1/4"]
Gas pipe
ø12.7 [1/2"]
18 - 54 models
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø15.88 [5/8"]
72 model
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø19.05 [3/4"]
96 model
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø22.2 [7/8"]
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......