[5-2 Outdoor Unit Control ]
HWE18240_GB
chapter 5 -
19
5 Control
5-2-16
Emergency Operation Mode
1. Problems with the outdoor unit
Emergency operation mode is a mode in which outdoor units that are operating normally take over the operation of the out-
door units that are experiencing problems. (HP144-HP240T(Y)SNU models go into an emergency operation mode when one
outdoor unit is in trouble.)
This mode can be started by performing an error reset via the remote controller.
(1) Starting the emergency operation
1) When an error occurs, the error source and the error code will be displayed on the display on the remote controller.
2) The error is reset using the remote controller.
3) If an error code appears that permits an emergency operation in step 1) above, (See the table below.), the retry operation
starts.
4) If the same error is detected during the retry operation (step 3 above), an emergency operation can be started by resetting
the error via the remote controller.
Error codes that permit an emergency operation (Applicable to both OC and OS)
Emergency operation pattern (2 outdoor units)
Trouble source
Error codes that permit an
emergency operation
Error code description
Compressor
Fan motor
Inverter
0403
Serial communication error
4220,4225,4226
Bus voltage drop
4230,4235
Heatsink overheat protection
4240,4245
Overload protection
4250,4255,4256
Overcurrent relay trip
5110
Heatsink temperature sensor failure (THHS)
5120
DCL temperature sensor circuit fault
5301
Current sensor/circuit failure
5305,5306
Position error
Thermistor
TH2
5102
Subcool heat exchanger bypass outlet temperature sensor failure
TH3
5103
Pipe temperature sensor failure
TH4
5104
Discharge temperature sensor failure
TH5
5105
Accumulator inlet temperature sensor failure
TH6
5106
Subcool heat exchanger liquid outlet sensor failure
TH7
5107
Outside air temperature sensor failure
TH15
5115
Compressor shell bottom temperature sensor fault
Power
4102
Open phase
4115
Power supply sync signal abnormality
OC
OC failure
pattern
Trouble
Normal
Permitted Permitted
Permitted Permitted
60%
Cooling
Heating
Normal
Trouble
OS failure
pattern
OS
Emergency
operation
Maximum total capacity
of indoor units (Note 1)
(Note 1) If an attempt is made to put into operation a group of indoor units whose total capacity exceeds the maximum allowable capacity,
some of the indoor units will go into the same condition as Thermo-OFF.
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......