[2-7 Example System with an MA Remote Controller ]
HWE18240_GB
14
-
chapter 2
2 Restrictions
2-7-2
Single Refrigerant System with Two or More LOSSNAY Units
(1) Sample control wiring
(2) Cautions
1) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) A transmission booster is required in a system to which
more than 32 indoor units (26 units if one or more indoor
units of the 72 model or above is connected) are con-
nected.
Refer to the DATABOOK for further information about
how many booster units are required for a given system.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as 2-7-1
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Same as 2-7-1
L2
TB3
51
52
TB7
S
TB3
TB7
S
IC
TB5
S
TB15
1 2
01
IC
TB5
S
TB15
1 2
02
A B
MA
A B
MA
LC
TB5
S
05
IC
TB5
S
1 2
TB15
IC
TB5
S
TB15
1 2
04
03
LC
TB5
S
06
A B
MA
Group
Group
Group
M1 M2 M1
M2 M1
M2
M1 M2
M1 M2
M1 M2
L1
1
L3 L4
L12 L13
53
TB7
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
S
TB3
L1
OC
OS1
OS2
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
Interlock operation with
the ventilation unit
m1
m2
m3
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......