[2-10 Restrictions on Refrigerant Pipes ]
30
-
chapter 2
HWE18240_GB
2 Restrictions
(3) Size of the refrigerant pipe between the branches for connection to indoor units
(4) Size of the refrigerant pipe between the first distributor and the second distributor
(5) Size of the refrigerant pipe between the first distributor or the second distributor and outdoor
units
Total capacity of the
downstream units
Liquid pipe size (mm) [inch]
Gas pipe size (mm) [inch]
- 54
ø9.52 [3/8"]
ø15.88 [5/8"]
P55 - P72
ø9.52 [3/8"]
ø19.05 [3/4"]
P73 - P108
ø9.52 [3/8"]
ø22.2 [7/8"]
P109 - P144
ø12.7 [1/2"]
ø28.58 [1-1/8"]
P145 - P240
ø15.88 [5/8"]
ø28.58 [1-1/8"]
P241 - P308
ø19.05 [3/4"]
ø34.93 [1-3/8"]
P309 -
ø19.05 [3/4"]
ø41.28 [1-5/8"]
Liquid pipe size (mm) [inch]
Gas pipe size (mm) [inch]
ø19.05 [3/4"]
ø34.93 [1-3/8"]
Liquid pipe size (mm) [inch] Gas pipe size (mm) [inch]
72 model
ø9.52 [3/8"]
ø22.2 [7/8"]
96 model
120 model
ø12.7 [1/2"]
ø28.58 [1-1/8"]