[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
HWE18240_GB
chapter 7 -
49
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-8-8
Error Code [6607] Error Source Address = Outdoor Unit (OC)
1. Error code definition
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Incidental cause
1)
Turn off the power source of the outdoor unit, and
turn it on again.
(2)
Contact failure of transmission line of OC or IC
2)
If the error is accidental, it will run normally. If not,
check the causes (2) - (5).
(3)
Decrease of transmission line voltage/signal by exceed-
ing acceptable range of transmission wiring.
Farthest: 200 m [656ft] or less
Remote controller wiring:
10m [32ft] or less
(4)
Erroneous sizing of transmission line (Not within the
range below).
Wire diameter:
1.25mm
2
[AWG16] or more
(5)
Outdoor unit control board failure
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......