[5-2 Outdoor Unit Control ]
HWE18240_GB
chapter 5 -
15
5 Control
5-2-8
Continuous heating mode control
(1) Continuous heating mode start conditions
Continuous heating mode will start when all the conditions listed in the table below are met (outside temperature, cumulative
compressor operation time, and piping temperature).
SW4 (848) must be set to ON to perform Continuous heating mode.
(2) Valve operation during Continuous heating cycle
1) HP72-120
Outside temperature (TH7)
2.0 °C [35.6 °F] to 7.0 °C [44.6 °F]
Cumulative compressor operation
time
After 10 minutes at 2.0 °C [35.6 °F] to 3.5 °C [38.3 °F] has elapsed
After 20 minutes at 3.6 °C [38.5 °F] to 7.0 °C [44.6 °F] has elapsed
Evaporating temperature (Te)
After 3 minutes at 0°C [32°F] to -25 °C [-13°F] has elapsed
Front (bottom) HEX in defrost cycle
Rear (front) HEX in defrost cycle
Outdoor unit fan
Left fan: Fixed time control
Right fan: 0%
Right fan: 0%
Left fan: Fixed time control
SV1a
OFF
SV2
OFF
SV9
ON
SV10
ON
OFF
21S4a
ON ON
21S4b
ON OFF