[2-10 Restrictions on Refrigerant Pipes ]
28
-
chapter 2
HWE18240_GB
2 Restrictions
When the vertical separation between indoor units exceeds 15 m
Outdoor unit above indoor unit
example 1
example 2
When the distance from the first branch to the farthest indoor unit
exceeds 40 m
Outdoor unit below indoor unit
example 3
example 4
When the distance from the first branch to the farthest indoor unit
exceeds 40 m and the vertical separation between indoor units
exceeds 15 m
example 5
Outdoor
unit
Increase the size of the pipe indicated by
"A, a1, and a2" by one size.
H:exceeds 15 m
A
H
B
a1
a2
b1
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Increase the size of the pipe indicated by
"A, B, C, D, E, b1 and e1" by one size.
H1:exceeds 15 m
H2:15 m or less
C
D
c
A
B
H2
H1
d
e2
e1
E
a
b2
b1
Outdoor
unit
Outdoor
unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor
unit
Increase the size of the pipe indicated by "A, a1, and a2" by one size.
H:exceeds 15 m
B
H
A
a1
a2
b
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
L1
C
D
c
A
B
L2
d
e2
e1
E
a
b2
b1
Increase the size of the pipe indicated by "E, e1, e2 and b1" by one size.
H:15 m or less
L1, L2:40m
Outdoor
unit
Outdoor
unit
H
Indoor unit
Indoor unit
Indoor unit
Outdoor
unit
Outdoor
unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
L1
C
D
c
A
B
L2
d
e2
H2
H1
e1
E
a
b2
b1
e1
Increase the size of the pipe indicated by
"A, B, C, D, E, e1, e2 and b1" by one size.
H1:exceeds 15 m
H2:15 m or less
L1, L2:40m
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......