[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
HWE18240_GB
chapter 7 -
33
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-6-22
Error Codes [4250, 4255, 4256] Detail Code 104
1. Error code definition
Short-circuited IPM/Ground fault (Detail code 104)
2. Error definition and error detection method
When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.
3. Cause, check method and remedy
In the case of 4250
In the case of 4255 and 4256
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
Grounding fault compressor
Refer to the following page(s).
[8-9-3 Checking the Compressor for Ground Fault and Coil Resistance
Problems]
(2)
Inverter output related
Refer to the following page(s).
[8-9-2 Checking the Inverter Board Error Detection Circuit]
[8-9-3 Checking the Compressor for Ground Fault and Coil Resistance
Problems]
[8-9-4 Checking the Inverter for Damage at No-Load]
[8-9-5 Checking the Inverter for Damage during Compressor Operation]
[8-9-11 Checking the Installation Conditions]
Cause
Check method and remedy
(1)
Grounding fault of fan motor
Refer to the following page(s).
[8-9-7 Checking the Fan Motor for Ground Fault and Coil Resistance
Problems]
(2)
Fan board failure
Refer to the following page(s).
[8-9-8 Checking the Fan Board Error Detection Circuit at No Load]
[8-9-9 Checking the Fan Board for Damage at No Load]
[8-9-10 Checking the Fan Board for Damage with Load]
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......