[3-3 Functions of the Major Components of Outdoor Unit ]
HWE18240_GB
chapter 3 -
5
3 Major Components, Their Fu
nctions and Refrigerant Circuits
Thermis-
tor
TH4
(Discharge
temperature)
1) Detects discharge air temper-
ature
2) Provides high-pressure pro-
tection
Degrees Celsius
Resistance check
0°C[32°F] :698 k
ȍ
10°C[50°F] :413 k
ȍ
20°C[68°F] :250 k
ȍ
30°C[86°F] :160 k
ȍ
40°C[104°F] :104 k
ȍ
50°C[122°F] : 70 k
ȍ
60°C[140°F] : 48 k
ȍ
70°C[158°F] : 34 k
ȍ
80°C[176°F] : 24 k
ȍ
90°C[194°F] :17.5 k
ȍ
100°C[212°F] :13.0 k
ȍ
110°C[230°F] : 9.8 k
ȍ
TH2
(Pipe
temperature)
LEV 1 is controlled based on the
TH2, TH3, and TH6 values.
Degrees Celsius
0°C[32°F] :15 k
ȍ
10°C[50°F] :9.7 k
ȍ
20°C[68°F] :6.4 k
ȍ
25°C[77°F] :5.3 k
ȍ
30°C[86°F] :4.3 k
ȍ
40°C[104°F] :3.1 k
ȍ
Resistance check
TH3
(Pipe
temperature)
1) Controls frequency
2) LEV1 is controlled based on
the subcool at heat exchange
outlet that is obtained based
on the HPS data and TH3 val-
ue.
TH7
(Outdoor
temperature)
1) Detects outdoor air tempera-
ture
2) Controls fan operation
TH5
(Pipe
temperature)
LEV2 are controlled based on the
63LS and TH5 values.
TH6
(Pipe
temperature)
Controls LEV1 based on TH2,
TH3, and TH6 data.
TH15
(Compres-
sor shell bot-
tom
temperature)
Detects compressor shell bottom
temperature
THHS
Inverter
heat sink
temperature
IPM is
built in.
Do not at-
tempt to
measure
resis-
tance.
Inverter overheating protection
Degrees Celsius
0°C[32°F] :161 k
ȍ
10°C[50°F] :97 k
ȍ
20°C[68°F] :60 k
ȍ
25°C[77°F] :48 k
ȍ
30°C[86°F] :39 k
ȍ
40°C[104°F] :25 k
ȍ
-
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check method
R = 7.465k
120
R = 4057
R =
7.465
25/120
t
4057
273 t
1
393
1
exp
R = 15k
0
R = 3460
R = 15
0/80
t
3460
273 t
1
273
1
exp
R = 17k
50
R = 4016
R = 17
25/120
t
4016
273 t
1
323
1
exp
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......