[8-10 Control Circuit ]
HWE18240_GB
chapter 8 -
45
8 Troubleshooting Based on Observed Symptoms
2) TNU
AC power source (TNU: 208-230 VAC)
Control system (5-30 VDC)
TB2
TB15
TB5
* MA remote controllers and ME remote controllers cannot be used together.
(Both the ME and MA remote controller can be connected to a system with a system controller.)
A, B
A, B
220-240 VAC
AC Power source
To next unit
(Indoor unit)
MA
remote controller wiring
(Non-polar 2 wire)
17-30 VDC
9-12 VDC
Terminal block for
power source
Terminal block
for MA remote
controller
Terminal block
for transmission
line connection
17-30 VDC
Terminal block for
transmission line
for centralized control
(24-30 VDC)
TB7
Indoor/outdoor
transmission block
(24-30 VDC)
TB3
ME remote
controller
MA remote
controller
Indoor unit
M-NET
transmission line
(Non-polar 2 wire)
TB1
AC Power source
TNU: 208-230 VAC
Power-supply terminal
block
Outdoor unit
CN40
Inverter board
Rectifier
Rectifier
72C
DCL
5 V power supply
Smoothing capacitor
Inverter
Microcomputer
Inverter
drive circuit
Compressor
Noise filter
Fuse
Fuse
Surge protector
Solenoid valve
Four-way valve
Control board
Fuse
Microcomputer
FAN board
Fuse
Heat exchanger fan
Microcomputer
5 V power supply
FAN board
Fuse
Heat exchanger fan
Microcomputer
5 V power supply
Transmission
power-supply
detection circuit
Relay drive circuit
Inverter-
reset circuit
Relay/LEV
drive circuit
Noise filter board
Capacitor board
Power-supply
detection circuit
USB circuit
DC-DC
converter
DC-DC
converter
Circulating fan
control circuit
Regulator
5 V
power supply
18 V power supply
DC-DC
converter
30 V power supply
17 V power supply
DC-DC
converter
24 V power supply
9 V power supply
12 V power supply
3.3 V
power supply
Power-supply board
72C
LEV
Filter board
Noise filter
Circulating fan
Inverter
drive circuit
Inverter
Inverter
drive circuit
Inverter
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......