[8-7 Troubleshooting Outdoor Unit Fan Problems ]
24
-
chapter 8
HWE18240_GB
8 Troubleshooting Based on Observed Symptoms
8-7
Troubleshooting Outdoor Unit Fan Problems
(1) Fan motor (common items)
To check the revolution of the fan, check the inverter output state on the self-diagnosis LED, as the inverter on the outdoor
fan controls the revolutions of the fan.
When starting the fan, the fan runs at full speed for 5 seconds.
When setting the DIP SW4 (when SW6-10 is set to OFF) as shown in the figure below, the inverter output [%] will appear.
100% indicates the full speed and 0% indicates the stopping.
As the revolution of the fan changes under control, at the interphase or when the indoor unit operation capacity is low, the
revolution of the fan may change.
If the fan does not move or it vibrates, fan board problem or fan motor problem is suspected. When checking the fan motor
for problems by shutting down the power, be sure to disconnect the motor wire from the fan board. (If a short-circuited fan
board malfunctions, it will keep the fan motor from rotating smoothly.) For details, refer to the following page(s).
[8-9-6 Checking the Fan Motor for Ground Fault and Coil Resistance Problems]
[8-9-7 Checking the Fan Board Error Detection Circuit at No Load]
[8-9-8 Checking the Fan Board for Damage at No Load]
[8-9-9 Checking the Fan Board for Damage with Load]
Fan 1
Fan 2
SW4
SW4
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......