[3-3 Functions of the Major Components of Outdoor Unit ]
6
-
chapter 3
HWE18240_GB
3 Major Components, Their Fu
nctions and Refrigerant Circuits
Sole-
noid
valve
SV1a
Discharge-
suction
bypass
1) High/low pressure bypass at
start-up and stopping, and
capacity control during low-
load operation
2) High-pressure-rise preven-
tion
AC208-230V
Open while being powered/
closed while not being pow-
ered
Continuity check
with a tester
SV2
Makes excessive refrigerant in the
accumulator evaporate
Open while being powered/
closed while not being pow-
ered
SV9
High-pressure-rise prevention
Open while being powered/
closed while not being pow-
ered
SV10
Continuous heating cycle mode
Open while being powered/
closed while not being pow-
ered
Linear
expan-
sion
valve
LEV1
(SC control)
Adjusts the amount of bypass flow
from the liquid pipe on the outdoor
unit during cooling
DC12V
Opening of a valve driven by a
stepping motor 0-480 pulses
Same as indoor
LEV
The resistance val-
ue differs from that
of the indoor LEV.
Refer to the follow-
ing page(s). [8-8
Troubleshooting
LEV Problems]
LEV9
(Refrigerant
flow adjust-
ment)
Adjusts the flow of refrigerant by-
passed from the pipe for cooling
the control board when the control
board temperature rises
LEV4
(Refrigerant
flow adjust-
ment)
Controls the bypassed refrigerant
flow to the compressor to sup-
press rises in the discharge tem-
perature (TH4).
LEV2a
(Refrigerant
flow adjust-
ment)
Adjusts refrigerant flow during
heating
Cut off the refrigerant flow during
continuous heating cycle
DC12V
Opening of a valve driven by a
stepping motor 2100 pulses
(Max. 3000 pulses)
Continuity Test with
a Tester.
Continuity between
white and orange.
Continuity between
yellow, red, and
blue.
LEV2b
(Refrigerant
flow adjust-
ment)
4-way
valve
21S4a
Changeover between heating and
cooling
AC208-230V
Dead: cooling cycle
Live: heating cycle
Continuity check
with a tester
21S4b
1) Changeover between heating
and cooling
2) Controls outdoor unit heat ex-
changer capacity
AC208-230V
Dead: cooling cycle
Outdoor unit heat exchanger
capacity at 100%
Live: heating cycle
Outdoor unit heat exchanger
capacity at 25%, 50%
or heating cycle
Fan
motor
FAN motor
1,2
Regulates the heat exchanger ca-
pacity by adjusting the operating
frequency and operating the pro-
peller fan based on the operating
pressure.
AC380-460V, 460W (YNU)
AC200-230V, 460W (TNU)
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check method
Yellow
White
Orange
red
Blue
M
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......