[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
HWE18240_GB
chapter 7 -
35
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-6-24
Error Codes [4250, 4255, 4256] Detail Codes 106 and 107
1. Error code definition
Instantaneous overcurrent (Detail code 106)
Overcurrent (effective value) (Detail code 107)
2. Error definition and error detection method
When a current above the specified value is detected by the electric current sensor.
Refer to the relevant pages for the details of model names and the specified values.
3. Cause, check method and remedy
In the case of 4250
In the case of 4255 and 4256
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
Inverter output related
Refer to the following page(s).
[8-9-2 Checking the Inverter Board Error Detection Circuit]
[8-9-3 Checking the Compressor for Ground Fault and Coil Resistance Problems]
[8-9-4 Checking the Inverter for Damage at No-Load]
[8-9-5 Checking the Inverter for Damage during Compressor Operation]
[8-9-11 Checking the Installation Conditions]
Check the IGBT module resistance value of the INV board, if no problems are
found.
[8-9-15 Troubleshooting Problems with IGBT Module]
(2)
The model selection
switches (SW5-3 - 5-8) on
the outdoor unit are set in-
correctly.
Check the setting for the model selection switch on the outdoor unit (Dipswitches
SW5-3 - 5-8 on the outdoor unit control board).
For switch settings, refer to the following page(s). [7-9-2 Error Code [7101]]
Cause
Check method and remedy
(1)
Fan board failure
Refer to the following page(s).
[8-9-8 Checking the Fan Board Error Detection Circuit at No Load]
[8-9-9 Checking the Fan Board for Damage at No Load]
[8-9-10 Checking the Fan Board for Damage with Load]
(2)
Outdoor unit fan failure
Check the outdoor unit fan for proper operation.
Check the fan motor if problems are found with the operation of the fan.
Refer to the following page(s). [8-9-7 Checking the Fan Motor for Ground Fault
and Coil Resistance Problems]
(3)
Air passage blockage
Check that the heat sink cooling air passage is not blocked
(4)
The model selection
switches (SW5-3 - 5-8) on
the outdoor unit are set in-
correctly.
Check the setting for the model selection switch on the outdoor unit (Dipswitches
SW5-3 - 5-8 on the outdoor unit control board).
For switch settings, refer to the following page(s). [7-9-2 Error Code [7101]]
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......