[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
64
-
chapter 7
HWE18240_GB
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-8-23
Error Code [6843]
1. Error code definition
A control communication start bit detection error
2. Error definition and error detection method
Indoor/outdoor unit communication error
Abnormal if indoor controller board could not receive any signal normally for 6 minutes after turning the power on.
Abnormal if indoor controller board could not receive any signal normally for 3 minutes.
Consider the unit as abnormal under the following condition. When 2 or more indoor units are connected to an outdoor unit,
indoor controller board could not receive a signal for 3 minutes from outdoor controller circuit board, a signal which allows
outdoor controller circuit board to transmit signals.
3. Cause, check method and remedy
1. Error code definition
A control communication start bit detection error
2. Error definition and error detection method
Indoor/outdoor unit communication error (Outdoor unit)
Abnormal if outdoor controller circuit board could not receive anything normally for 3 minutes.
3. Cause, check method and remedy
Note: Refer also to the Service Handbook for the indoor units.
Cause
Check method and remedy
(1)
Contact failure, short circuit or miswiring (converse wiring) of in-
door/outdoor unit connecting wire
Check disconnecting or looseness of indoor
/outdoor unit connecting wire of all indoor
units or outdoor units.
(2)
Defective transmitting receiving circuit of outdoor controller cir-
cuit board.
Turn the power off, and on again to check. If
abnormality generates again, replace indoor
controller board or outdoor controller circuit
board.
Note: other indoor controller board may have
defect.
(3)
Defective transmitting receiving circuit of indoor controller board.
(4)
Noise has entered into indoor/outdoor unit connecting wire.
(5)
Defective fan motor
Turn the power off, and detach fan motor
from connector (CNF1, 2). Then turn the
power on again. If abnormality is not dis-
played, replace fan motor. If abnormality is
displayed, replace outdoor controller circuit
board.
(6)
Defective rush current resistor of outdoor power circuit board
Check the rush current resistor on outdoor
power circuit board with tester. If open is de-
tected, replace the power circuit board.
Cause
Check method and remedy
(1)
Contact failure of indoor/outdoor unit connecting wire
Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor or out-
door units.
(2)
Defective communication circuit of outdoor controller circuit
board
Turn the power off, and on again to check.
Replace indoor controller board or outdoor
controller circuit board if abnormality is dis-
played again.
(3)
Defective communication circuit of indoor controller board
(4)
Noise has entered into indoor/outdoor unit connecting wire.
Summary of Contents for PUHY-HP120TNU-A
Page 1: ......
Page 11: ...HWE18240_GB ...
Page 27: ...HWE18240_GB ...
Page 59: ...HWE18240_GB ...
Page 69: ...HWE18240_GB ...
Page 87: ...HWE18240_GB ...
Page 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Page 111: ...HWE18240_GB ...
Page 121: ...HWE18240_GB ...
Page 279: ...HWE18240_GB ...
Page 297: ...HWE18240_GB ...
Page 324: ......