3. SIGNALS AND WIRING
3.11 Servo amplifier terminal block (TE2) wiring method
POINT
Refer to Table 13.1 2) and 4) in section 13.2.1 for the wire sizes used for
wiring.
3.11.1 For the servo amplifier produced later than Jan. 2006
(1) Termination of the cables
(a) Solid wire
After the sheath has been stripped, the cable can be used as it is.
Sheath
Core
Approx. 10mm
(b) Twisted wire
1) When the wire is inserted directly
Use the cable after stripping the sheath and twisting the core. At this time, take care to avoid a
short caused by the loose wires of the core and the adjacent pole. Do not solder the core as it may
cause a contact fault. Alternatively, a bar terminal may be used to put the wires together.
2) When the wires are put together
Using a bar terminal.
Cable Size
Bar Terminal Type
[mm
2]
AWG
For 1 cable
For 2 cables
Crimping Tool
Manufacturer
1.25/1.5
16
AI1.5-10BK
AI-TWIN 1.5-10BK
2/2.5
14
AI2.5-10BU
CRIMPFOX ZA 3
Phoenix Contact
Cut the wire running out of bar terminal to less than 0.5mm.
Less than 0.5mm
When using a bar terminal for two wires, insert the wires in the direction where the insulation
sleeve does not interfere with the next pole and pressure them.
Pressure
Pressure
Summary of Contents for MR-J2S-*A
Page 13: ...WWW NNC IR A 12 MEMO ...
Page 117: ...WWW NNC IR 3 70 3 SIGNALS AND WIRING MEMO ...
Page 185: ...WWW NNC IR 7 12 7 GENERAL GAIN ADJUSTMENT MEMO ...
Page 195: ...WWW NNC IR 8 10 8 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 197: ...WWW NNC IR 9 2 9 INSPECTION MEMO ...
Page 221: ...WWW NNC IR 11 10 11 OUTLINE DIMENSION DRAWINGS MEMO ...
Page 293: ...WWW NNC IR 13 64 13 OPTIONS AND AUXILIARY EQUIPMENT MEMO ...
Page 321: ...WWW NNC IR 14 28 14 COMMUNICATION FUNCTIONS MEMO ...
Page 389: ...WWW NNC IR 15 68 15 ABSOLUTE POSITION DETECTION SYSTEM MEMO ...