1. TROUBLESHOOTING FOR SERVO AMPLIFIER (DRIVE UNIT)
1 - 88
Alarm No.: 8D
Name: CC-Link IE communication error
Alarm content
MR-J3-T10 came off.
An error occurred in CC-Link IE communication.
Detail
No.
Detail name
Cause
Check method
Check result
Action
Target
8D.1 CC-Link
IE
communication
error 1
(1) The MR-J3-T10 came
off during the CC-Link
IE communication.
Check if [AL. 74
Option card error 1]
occurred with alarm
history.
It is occurring.
Check it with the
check method for
[AL. 74].
[RJ010]
It did not occur.
Check (2).
(2) The Ethernet cable was
disconnected.
Check the Ethernet
cable connection.
It is disconnected.
Turn off the control
circuit power
supply of the servo
amplifier, and then
connect the
Ethernet cable.
[RJ010]
[GF]
It is connected.
Check (3).
(3) The CC-Link IE
communication was
disconnected by using
a wrong procedure.
Check if the
communication was
disconnected by
using the correct
procedure.
The communication
was disconnected by
using a wrong
procedure.
Follow the correct
procedure for
disconnecting the
communication.
The
communication
was disconnected by
using the correct
procedure.
Check (4).
(4) The wiring of the
Ethernet cable was
incorrect.
Check if the wiring of
Ethernet cable is
correct.
The wiring is incorrect. Wire it correctly.
The wiring is correct.
Check (5).
(5) An Ethernet cable was
disconnected.
Check if the Ethernet
cable is
malfunctioning.
It has a failure.
Replace the
Ethernet cable.
It has no failure.
Check (6).
(6)
The
transmission
status of the CC-Link
IE communication is
abnormal.
Check the noise,
ambient temperature,
etc.
It has a failure.
Take
countermeasures
against its cause.
It has no failure.
Check (7).
(7)
MR-J3-T10
is
malfunctioning.
Replace the MR-J3-
T10, and then check
the repeatability.
It is not repeatable.
Replace the MR-
J3-T10.
It is repeatable.
Check (8).
(8) The servo amplifier is
malfunctioning.
Replace the servo
amplifier, and then
check the
repeatability.
It is not repeatable.
Replace the servo
amplifier.
[RJ010]
It is repeatable.
Check (9).
(9) The master station is
malfunctioning.
Check if the master
station is
malfunctioning.
It has a failure.
Replace the master
station.
[RJ010]
[GF]
8D.2 CC-Link
IE
communication
error 2
Check it with the check method for [AL. 8D.1].
8D.3 Master
station
setting error 1
(1) The station No. is set to
a value other than 1 to
120 with the master
station.
Check the [Pr. Po02]
setting.
The setting value is
incorrect.
Set it correctly.
[RJ010]
The setting value is
correct.
Check (2).
(2) The network number is
set to a value other
than 1 to 239 with the
master station.
Check the [Pr. Po03]
setting.
The setting value is
incorrect.
Set it correctly.
The setting value is
correct.
Check (3).
(3)
MR-J3-T10
is
malfunctioning.
Replace the MR-J3-
T10, and then check
the repeatability.
It is not repeatable.
Replace the MR-
J3-T10.
It is repeatable.
Check (4).
(4) The servo amplifier is
malfunctioning.
Replace the servo
amplifier, and then
check the
repeatability.
It is not repeatable.
Replace the servo
amplifier.
It is repeatable.
Check (5).
(5) The master station is
malfunctioning.
Check if the master
station is
malfunctioning.
It has a failure.
Replace the master
station.
Summary of Contents for MELSERVO MR-J4-B-RJ Series
Page 7: ...2 MEMO ...
Page 137: ...1 TROUBLESHOOTING FOR SERVO AMPLIFIER DRIVE UNIT 1 130 MEMO ...
Page 145: ...2 TROUBLESHOOTING FOR MR CV_POWER REGENERATION CONVERTER UNIT 2 8 MEMO ...
Page 155: ...3 TROUBLESHOOTING FOR MR CR55K 4 RESISTANCE REGENERATION CONVERTER UNIT 3 10 MEMO ...
Page 171: ...MEMO ...