1. TROUBLESHOOTING FOR SERVO AMPLIFIER (DRIVE UNIT)
1 - 125
Description
Possible cause
Check result
Action
Target
The position deviates during
operation after home position
return.
Frequency of the pulse train
command is too high.
Check the pulse train
command frequency is within
the range of specifications.
It is 500 kpulses/s or less for
the open-collector type. It is
4 Mpulses/s or less for the
differential line driver type.
Review the pulse train
command frequency. Select
a filter according to the pulse
train command frequency
from "Command input pulse
train filter selection" in [Pr.
PA13].
[A]
A cable for command is too
long.
Check the ripple of the
command frequency with
oscilloscope.
Shorten the wiring length.
Cable length must be 10 m
or shorter for differential line
driver output and 2 m or
shorter for open-collector
output.
SON (Servo-on) turned off
during operation.
Check if SON (Servo-on) is
off during operation using
status display or MR
Configurator2.
Review the wiring and
sequence not to turn off SON
(Servo-on) during operation.
CR (Clear) or RES (Reset)
turned on during operation.
Check if CR (Clear) or RES
(Reset) is on during operation
using status display or MR
Configurator2.
Review the wiring and
sequence not to turn on CR
(Clear) or RES (Reset)
during operation.
The setting of point tables
and start timing is incorrect.
Check if a time period from
after switching timings of
point table setting value and
point table No. until a start
timing is 3 ms or more.
Review the point table
setting.
Review the start timing.
An input signal to the MR-
D01 extension IO unit is
incorrect.
Check the selection of the
point table No. selection 1 to
point table No. selection 8
and check the wiring.
Check the input signal switch
to the MR-D01 extension IO
unit and check the wiring.
The program, start timing, etc.
are incorrect.
Check if a time period from
after switching timings of
BCD input program and point
table No. until a start timing
is 3 ms or more, etc.
Review the controller
programs.
The setting of MR-DS60
digital switch is incorrect.
Check the [Pr. Po10] setting. Review the [Pr. Po10]
setting.
The wiring between MR-DS60
digital switch and MR-D01
extension IO unit is incorrect.
Check the wiring between
MR-DS60 digital switch and
MR-D01 extension IO unit.
Review the wiring between
MR-DS60 digital switch and
MR-D01 extension IO unit.
Wiring of the MR-HDP01
manual pulse generator or
setting of "manual pulse
generator multiplication" ([Pr.
PT03], TP0 (manual pulse
generator multiplication 1),
TP1 (manual pulse generator
multiplication 2)) is incorrect.
The input value from the MR-
HDP01 manual pulse
generator and the command
position do not match.
Review the wiring.
Set the multiplication setting
correctly.
A mechanical slip occurred.
Or the backlash of the
machine part is large.
Check if there is a slip or
backlash on the machine part.
Adjust the machine part.
[A]
[B]
[WB]
[RJ010]
[GF]
Summary of Contents for MELSERVO MR-J4-B-RJ Series
Page 7: ...2 MEMO ...
Page 137: ...1 TROUBLESHOOTING FOR SERVO AMPLIFIER DRIVE UNIT 1 130 MEMO ...
Page 145: ...2 TROUBLESHOOTING FOR MR CV_POWER REGENERATION CONVERTER UNIT 2 8 MEMO ...
Page 155: ...3 TROUBLESHOOTING FOR MR CR55K 4 RESISTANCE REGENERATION CONVERTER UNIT 3 10 MEMO ...
Page 171: ...MEMO ...