3. TROUBLESHOOTING FOR MR-CR55K(4) RESISTANCE REGENERATION CONVERTER UNIT
3 - 9
No.
Name/Description
Cause
Check method
Check result
Action
91 Converter
overheat
warning
The temperature
of the resistance
regeneration
converter unit
heat sink reached
a warning level.
(1) Operated in the
overloaded status.
Check the effective
load ratio.
The effective load
ratio is high.
Check operation
pattern.
The effective load
ratio is small.
Check (2).
(2) Ambient temperature of
resistance regeneration
converter unit is over
55
˚
C.
Check the ambient
temperature.
It is over 55
˚
C.
Lower the ambient
temperature.
It is less than 55
˚
C. Check
(3).
(3)
The
resistance
regeneration converter
unit is malfunctioning.
Replace the resistance
regeneration converter
unit, and then check
the repeatability.
It is not repeatable.
Replace the
resistance
regeneration
converter unit.
E0 Excessive
regeneration
warning
There is a
possibility that
regenerative
power may
exceed
permissible
regenerative
power of
regenerative
resistor
(regenerative
option).
(1) The
regenerative
power exceeded 85%
of the permissible
regenerative power of
the regenerative
resistor (regenerative
option).
Check the effective
load ratio.
It is 85% or more.
When the
regenerative option
is used.
Reduce the
frequency of
positioning.
Reduce the load.
Review the
regenerative
option capacity.
When the
regenerative option
is not used.
Use the
regenerative
option.
E1 Overload warning 1
[A. 50 Overload 1]
or [A. 51
Overload 2] can
occur.
(1) Load increased to 85%
or more alarm level of
[A. 50 Overload 1] or
[A. 51 Overload 2].
Check it with the check method for [A.50] and [A.51].
E6 Converter
forced
stop warning
The EM1 (forced
stop) of the
resistance
regeneration
converter unit
was turned off.
(1) The EM1 (forced stop)
of the resistance
regeneration converter
unit was turned off.
Check the status of
the EM1 (forced stop)
of the resistance
regeneration
converter unit.
It is off.
Ensure safety and
turn on the EM1
(forced stop) of the
resistance
regeneration
converter unit.
It is on.
Check (2).
(2) The external 24 V DC
power supply is off.
Check if the external
24 V DC power supply
is inputted.
It is not inputted.
Input the 24 V DC
power supply.
It is inputted.
Check (3).
(3)
The
resistance
regeneration converter
unit is malfunctioning.
Replace the resistance
regeneration converter
unit, and then check
the repeatability.
It is not repeatable.
Replace the
resistance
regeneration
converter unit.
E8 Cooling fan speed
reduction warning
The cooling fan
speed decreased
to the warning
level or less.
(1) Foreign matter was
caught in the cooling
fan.
Check if a foreign
matter is caught in the
cooling fan.
Something has
been caught.
Remove the foreign
matter.
Nothing has been
caught.
Check (2).
(2) Cooling fan life expired. Check the total of
power on time of the
resistance
regeneration
converter unit.
It exceeds the
cooling fan life.
Replace the
resistance
regeneration
converter unit.
Summary of Contents for MELSERVO MR-J4-B-RJ Series