1. TROUBLESHOOTING FOR SERVO AMPLIFIER (DRIVE UNIT)
1 - 94
Alarm No.: 90
Name: Home position return incomplete warning
Alarm content
A home position return did not complete normally with the positioning function.
Detail
No.
Detail name
Cause
Check method
Check result
Action
Target
90.1 Home
position
return
incomplete
(5) A software stroke
limit/stroke limit was
detected.
In the I/O mode, check
if [AL. 99 Stroke limit
warning] occurred
when "_ _ _ 1" is set to
[Pr. PD12], or [AL. 98
Software stroke limit
warning] occurred
when "_ 1 _ _" is set to
[Pr. PD12].
[AL. 98 Software
stroke limit warning]
or [AL. 99 Stroke
limit warning]
occurred in the I/O
mode.
Move the machine
to within the limit
range, and then
make a home
position return.
When the home
position is fixed,
enable servo-on
again.
[GF]
[AL. 98 Software
stroke limit warning]
or [AL 99 Stroke
limit warning] did not
occur.
Or the motion mode
is set.
Check (6).
(6) ZP2 (Home position
return completion 2)
turned off after the
home position return
was executed.
Check if ZP2 (Home
position return
completion 2) is off.
ZP2 (Home position
return completion 2)
is off.
Check the conditions
in which ZP2 (Home
position return
completion 2) is off.
(Refer to section
2.1.2 and 5.1.2 of
"MR-J4-_GF_(-RJ)
Servo Amplifier
Instruction Manual
(I/O Mode)".)
Summary of Contents for MELSERVO MR-J4-B-RJ Series
Page 7: ...2 MEMO ...
Page 137: ...1 TROUBLESHOOTING FOR SERVO AMPLIFIER DRIVE UNIT 1 130 MEMO ...
Page 145: ...2 TROUBLESHOOTING FOR MR CV_POWER REGENERATION CONVERTER UNIT 2 8 MEMO ...
Page 155: ...3 TROUBLESHOOTING FOR MR CR55K 4 RESISTANCE REGENERATION CONVERTER UNIT 3 10 MEMO ...
Page 171: ...MEMO ...