'11 • PAC-T-160
(d) Timer operation
1) Sleep timer
Set the duration of time from the present to the time to turn off the air-conditioner.
It can be selected from 10 steps in the range from “OFF 1 hour later” to “OFF 10 hours later”. After the sleep timer
setting, the remaining time is displayed with progress of time in the unit of hour.
2) OFF timer
Time to turn OFF the air-conditioner can be set in the unit of 10 minutes.
3) ON timer
Time to turn ON the air-conditioner can be set. Indoor temperature can be set simultaneously.
4) Weekly timer
Timer operation (ON timer, OFF timer) can be set up to 4 times a day for each weekday.
5) Timer operations which can be set in combination
Sleep timer
OFF timer
ON timer
Weekly timer
Sleep timer
�
�
�
OFF timer
�
�
�
ON timer
�
�
�
Weekly timer
�
�
�
Note (1)
�
: Allowed
�
: Not
Item
Item
(e) Remote controller display during the operation stop
1) “Centralized control ON” is displayed always on the LCD under the “Center/Remote” and “Center” modes during the
operation stop (Power ON). This is not displayed under the “Remote” mode.
2) If this display is not shown under the “Center/Remote” mode, check if the indoor unit power switch is turned on or not.
(f)
Hot start (Cold draft prevention at heating)
At the startup of heating operation, at resetting of the thermostat, during defrost operation and at returning to heating, the
indoor fan is controlled by the indoor heat exchanger temperature (detected with Th
I
-R) for preventing the cold draft.
Judgment by heating start thermostat
Normal condition/Set airflow volume
Thermostat OFF
Thermostat ON
Compressor OFF
Compressor ON
End of defrosting
Heat exchanger temp. 35
˚C
or higher, or after 7 minutes
Heat exchanger temp. 35
˚C
or higher, or after 7 minutes
Defrosting start
Fan
Lo
Lo
Set airflow volume
Set airflow volume
Indoor heat exchanger temperature (˚C)
Indoor heat exchanger temperature (˚C)
35
35
45
25
35
Indoor heat exchanger temperature (˚C)
Set airflow volume
Fan
OFF
Lo
25
35
45
Set airflow volume
Fan
OFF
Indoor heat exchanger temperature (˚C)
Fan
Lo
(
1
)
Note (1) Heating preparation is displayed during the hot start (when the compressor is operating and the indoor fan does not provide the set airflow volume).