155
-
None
Power supply system error
(Power supply to indoor control PCB)
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is
AC220/240V
detected between 1 and
2 on the terminal block
of indoor
unit?
NO
NO
Are fuses OK (2 pcs.)?
YES
YES
YES
NO
Is the
check of resistance between
�
-
�
of CNW0
OK?
NO
Is the
checked result
of resistance of FM,
LM, etc
OK?
NO
NO
Note(1) F200, F201
(1)
(2)
Note (2)
�
for GND
Is DC5V
detected between
�
-
�
of CNW2?
NO
Is
AC380/415V
for 3-phase unit detected
between 1, 2 and 3 on the teminal
block of outdoor unit or is AC220/240V
for 1-phase unit detected between
1 and 2 on the terminal
block of outdoor
unit?
YES
YES
YES
YES
Is JX1 open?
Defective outdoor control
PCB (Noise filter)
Misconnection or breakage
of connecting wires
Defective indoor control or
power PCB
➞
Replace.
Replace FM, LM, etc.
Replace fuse.
Defective indoor power
PCB
➞
Replace.
Open JX1.
Defective indoor control
PCB
➞
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Misconnection or breakage of
connecting wires
• Blown fuse
• Faulty transformer
• Faulty indoor control or
power PCB
• Broken harness
• Faulty outdoor control PCB
(Noise filter)
Note:
Error code
Remote controller:
LED
Green
Red
Indoor Stays OFF Stays OFF
Outdoor Stays OFF 2 times flash
Content
'11 • PAC-T-160