181
–
'11 • PAC-T-160
E41
1. Applicable model
5. Troubleshooting
FDC200, 250 models
Diagnosis
Countermeasure
OK
Replace power transistor
Fix it properly
OK
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
Note:
Error code
Remote controller:
LED
Green
Red
Outdoor control PCB
Outdoor
inverter
PCB
1 time flash
Keeps flashing
Yellow
Indoor control PCB
Stays OFF
Keeps flashing
Content
6 times flash
Power transistor overheat (2/2)
(Model FDC200
,
250 only)
When anomalously high
temperature is detected by power
transistor temperature thermistor
(Tho-P1)
Anomalously high temperature
of power transistor is detected 5
times within 60 minutes.
• Inverter PCB anomaly
• Outdoor fan motor anomaly
• Improperly fixing of power
transistor to radiator fin
• Power transistor temperture
thermistor anomaly
• Inadequate installation space
of outdoor unit
Is it
possible to reset the error
for 10 minuted after compressor
stopped?
Can error be
reset?
NO
NO
YES
Is the
installation space of outdoor
unit enough ?
Is the outdoor fan running?
Replace inverter PCB
Are the
characteristics of power transitor
temperature thermistor
OK?
Is the
fixing of power transistor
to radiator fin OK?
Application of radiating silicone
Fixed screws
Correct it
Replace the outdoor fan motor
or the outdoor control PCB
Replace the power tansistor
temperature thermistor
Is the
connection of power transitor
temperature thermistor
connector OK?
Connect it securely
Does the error recur?
0
20
40
60
80
100
120
140
160
180
200
0
20
40
60
80
100
120
140
Temperature (°C)
Te
mperature thermistor resistance (k
Ω
)
Temperature-resistance characteristics
(Shot circuit)
(Broken wire)
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
* Characteristics of power transistor temperature thermistor