137
-
'11 • PAC-T-160
3) Model FDC200VS, 250VS
a)
Replace the inverter PCB after 10 minutes from power OFF. (Be sure to check that LED (LED1,2) of the inverter
PCB put out the lights. It measures that the voltage (AC) between terminals (R,S,T) on the noise filter PCB (see Fig 1)
is discharged sufficiently.)
b)
Remove the terminal on the terminal block (TB2) of the inverter PCB and the connector (CNR) of replace the PCB.
c) Make set switch (SW1,2) as shown in Table 1.
d) Connect the terminal of terminal block and the connector to the inverter PCB.
※
Remove the short bar form the PCB before the replacement.
Connect it with P2-P3 pins of PCB after the replacement.
Connector(CNR)
Terminal
block(TB2)
Parts Arrangement View
(the inverter PCB)
Parts No.
R,S,T
Noise filter
substrate
SW1,2
Fig. 1 The front of control
LED1,2
※
Table.1 Switch setting
In case of one substrate.
SW1-1
OFF
SW1-2
OFF
SW1-3
OFF
SW1-4
OFF
SW2-1
ON
SW2-2
OFF
SW2-3
OFF
SW2-4
OFF
PCB012D007C
K
Summary of Contents for FDF100VNVD
Page 81: ... 80 80 11 PAC T 160 ...
Page 82: ... 81 81 11 PAC T 160 ...
Page 83: ... 82 82 11 PAC T 160 ...