156
-
None
Power supply system error
(Power supply to remote controller)
Keeps flashing
Stays OFF
Keeps flashing 2 times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Isn't there any
loose connection of remote
controller wires?
Isn't remote
controller wire broken or
short-circuited?
Is DC180V
between
�
-
�
of
CNW2?
Disconnect remote
controller wires.
NO
Is DC15V or
higher detected between X-Y
of indoor unit terminal
block?
YES
YES
YES
YES
NO
NO
NO
Correct.
Replace wires.
Replace remote controller.
Defective indoor power
PCB
➞
Replace.
Defective indoor control
PCB
➞
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Remote controller wire
breakage/short-circuit
• Defective remote controller
• Malfunction by noise
• Faulty indoor power PCB
• Broken harness
• Faulty indoor control PCB
Note:
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
'11 • PAC-T-160
Summary of Contents for FDF100VNVD
Page 81: ... 80 80 11 PAC T 160 ...
Page 82: ... 81 81 11 PAC T 160 ...
Page 83: ... 82 82 11 PAC T 160 ...