180
–
'11 • PAC-T-160
E41
1. Applicable model
5. Troubleshooting
FDC71
~
140 models
Diagnosis
Countermeasure
Replace INV PCB
If not solved, replace
Noise filter PCB as well
Replace outdoor fan motor
Replace control PCB
If not solved, replace
INV PCB as well
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
Note: The "Single phase models" of inverter PAC have no function to output the signal for the power transistor overheat.
However since the power source for the power transistor and the outdoor fan motor is in the same line,
when the anomaly of the outdoor fan motor occurs, E41 is displayed.
Power transistor overheat (1/2)
(Model FDC71
~
140 only)
When less than 14VDC of
the output voltage is detected
between
➁
and
➂
on CNI3, E41
is displayed. (See "Note"
mentioned below)
When less than 14VDC of
the output voltage is detected
between
➁
and
➂
on CNI3, E41
is displayed. (See "Note"
mentioned below)
• Inverter PCB anomaly
• Outdoor fan motor anomaly
• Control PCB anomaly
• Noise filter PCB anomaly
Note (2) How to check the voltage between
�
and
�
of CNI3?
㹢
See E51
㩷
Is DC15V detected
between
�
and
�
on
①
Single phase models (FDC71-140)
②
3-phase models (FDC100-140)
ޓޓޓޓާ
E41
ިψ
Replace inverter PCB
CNI3?
NO
㩷
Is DC15V
deteted after disconnecting
outdoor fan motor?
Note (1): Under annomalous conditions,
the voltage becomes less than 14VDC.
(1) (2)
(1)
YES
YES
NO
Error code
Remote controller:
LED
Green
Red
Outdoor control PCB
Outdoor
inverter
PCB
1 time flash
Keeps flashing
Yellow
Indoor control PCB
Stays OFF
Keeps flashing
Content
6 times flash