When the outdoor unit
fan motor is anomalous:
(Refer to page 186)
TB1
PWB3
NOISE FILTER PWB
CT1
DM
52X
R1
R2
R3
R4
C1
C2
L1
L1
L1i
Red
White
Blue
Black
L2i
L3i
Ni
L1o
AC1
R5
+
4
-
6
K
G
1
2
3
4
AC3
AC2
L2o
L3o
No
3
2
E
L2
L3
N
1
2
3
P
P2
P3
N2
CNI3
CNI1
CNA1
CNFAN1
CNFAN2
CNEEV2
CNEEV1
CNM
CNS
CNR
CNH
CNE
CNW2
CNW
F
250V 10A
CNIP
THo-IPM
THo-A
THo-S
THo-D
THo-R1
THo-R2
THo-H
CNTH
LTP
CNU CNPS
CNA2
CNW1
CNO1
CNO2
N
2
U
U
V
V
W
W
CT1
CM
PWB2
INVERTER PWB
PWB4
DC FAN PWB
FMO1
FMO2
SM2
SM1
52X
20S
CH1
63H
RAM
F1 (250V 3A)
PWB1
CONTROL PWB
Models FDC200,250VS
●
Outdoor unit check points
Cheek items with the *mark when the power is ON.
LED2
(Red)
LED1
(Green)
LED2
(Red)
LED1
(Green)
F1 (250V, 3A)
Power supply check:
Measure the power supply L1,L2,L3
(It is normal if it is AC380-415V)
Noise filter check:
There should be continuity.
There should be no shorts between phases.
Resistance check:
Resistance is measured
(15
Ω
)
DC Reactor contiuity
check: 55m
Ω
or less
Capacitor check:
Check for anomaly in appearance
such as damage, swelling, etc.
Power transistor module check:
Check for burnout, open circuit or damage
(see page XXX for the check procedure).
Fuse check:There should
be continuity.
If it is faulty, replace the
inverter board.
Fuse check:There should be
continuity.
Red
White
Brown
LED2 (Red) Check
1 ~ 6 times flash
(Refer to page 121)
LED2 (Red) check:
1 ~ 5 time flash (Refer to page 121)