56
7 SETTINGS
7.1 Network Configuration Settings
Setting item list
When using the safety remote I/O module, always enable "Station-based Block Data Assurance" of the master
station. When it is disabled, correct operation of the safety remote I/O module cannot be guaranteed. For
"Station-based Block Data Assurance", refer to the following.
User's manual for the master station used
Item
Setting details
Setting range
RX Setting, RY Setting
Points
Set the assignment of RX/RY points.
0 to 16 (Default value: 16)
Start
The RX/RY start number is displayed.
End
The RX/RY end number is displayed.
RWr Setting, RWw Setting
Points
Set the assignment of RWr/RWw points.
0 to 16 (Default value: 4)
Start
The RWr/RWw start number is displayed.
End
The RWr/RWw end number is displayed.
Network Synchronous Communication
Set "Asynchronous" for the safety remote
I/O module.
• Asynchronous (Default value)
• Synchronous
Communication Period Setting
Set the cycle of the safety remote I/O
module when setting multiple
communication cycles. When the
communication speed differs between the
master station and the safety remote I/O
module, the setting range is limited. (
Page 54 Communication cycle interval
setting)
• Basic Period
• Normal-Speed
• Low-Speed