7 SETTINGS
7.2 Parameter Setting
59
7
Slave station parameter automatic setting
Slave station parameter automatic setting writes the parameters of the safety remote I/O module to the CPU module.
The parameters of the safety remote I/O module are saved in the CPU internal memory.
When the safety remote I/O module enters or returns to the network, the parameters of the safety remote I/O module are
automatically set via the master station. The parameters are written to the non-volatile memory of the safety remote I/O
module.
The safety remote I/O module starts data link with the master station after parameter automatic setting.
The status of parameter automatic setting can be checked with the remote register. (
• When the user authentication function of the CPU module is enabled, perform the logon of the user
authentication function in advance. (
Page 99 User Authentication Function)
• The parameters of the safety remote I/O module are not saved on the SD memory card.
Parameter setting
Operating procedure
1.
Open the "CC-Link IE TSN Configuration" window.
[Navigation window]
[Parameter]
[Module Information]
Model
[Basic Settings]
[Network Configuration
Settings]
2.
Select the safety remote I/O module in "Module List" and drag and drop it to the list of stations (1) or the network map (2).
"Station Type", "RX/RY Setting", and "RWw/RWr Setting" are automatically input. Change a value as necessary.
3.
Select the "Parameter Automatic Setting" check box.
(1)
(2)