APPX
Appendix 4 Remote Buffer Memory
145
A
■
Double input discrepancy detection setting
Set whether to detect double input discrepancy in units of 2 points.
• When "Wiring selection of input" is set to "0: Not used", "2: Safety single", or "3: General single", or when
"Fast logic pattern setting" is set to "4: Pattern 4", this parameter is ignored.
• When "Fast logic pattern setting" is set to "2: Pattern 2" or "3: Pattern 3", double input discrepancy detection
settings X6 and X7 are ignored.
■
Double input discrepancy auto recovery setting
Set whether or not to use auto recovery when a double input discrepancy detection error occurs, on a module-by-module
basis.
When "0: Not used", "2: Safety single", or "3: General single" is selected in "Wiring selection of input" for all
points, when "Fast logic pattern setting" is set to "4: Pattern 4", or when "Double input discrepancy detection
setting" is set to "1: Do not detect", double input discrepancy detection errors do not occur and thus auto
recovery is not performed.
■
Double input discrepancy detection time
Set the double input discrepancy detection time in units of 2 points.
• When "Wiring selection of input" is set to "0: Not used", "2: Safety single", or "3: General single", when "Fast
logic pattern setting" is set to "4: Pattern 4", or when "Double input discrepancy detection setting" is set to
"1: Do not detect", this parameter is ignored.
• When "Fast logic pattern setting" is set to "2: Pattern 2" or "3: Pattern 3", double input discrepancy detection
times X6 and X7 are ignored.
Module
Address (hexadecimal)
Name
Setting range
Default value
Input module
0130H to 0133H
Double input discrepancy detection
setting (X0, X1) to (X6, X7)
0: Detect
1: Do not detect
0: Detect
Output module
I/O combined module
0130H to 0133H
Module
Address (hexadecimal)
Name
Setting range
Default value
Input module
0140H
Double input discrepancy auto recovery
setting
0: Not used
1: Used
0: Not used
Output module
I/O combined module
0140H
Module
Address (hexadecimal)
Name
Setting range
Default value
Input module
0150H to 0153H
Double input discrepancy detection time
(X0, X1) to (X6, X7)
1 to 6000 (
10ms)
1 (
10ms)
Output module
I/O combined module
0150H to 0153H