APPX
Appendix 4 Remote Buffer Memory
147
A
■
Wiring selection of output
Set the wiring selection of output in units of 1 point.
• When Yn (n: even number) in "Wiring selection of output" is set to "1: Safety double wiring (Source/
Source)", only "1: Safety double wiring (Source/Source)" can be set for Yn+1. Outputting ON of a pair of
outputs turns on the output signal.
• For unused output terminals, set "0: Not used" in "Wiring selection of output".
• When Yn (n: even number) in "Wiring selection of output" is set to "0: Not used" or "2: Safety single", set a
value other than "1: Safety double wiring (Source/Source)" for Yn+1.
• When "Fast logic pattern setting" is set to other than "0: Not used", this parameter is ignored.
■
Output dark test execution setting
Set whether to perform the output dark test function of the diagnostic function in the safety remote I/O module in units of 1
point.
• When "Wiring selection of output" is set to "0: Not used", the points that are set to "0: Not used" ignore this
setting value.
• When "Wiring selection of output" Yn (n: even number) is set to "1: Safety double wiring (Source/Source)",
set the same value for "Output dark test execution setting" Yn and Yn+1, the partner of Yn.
Module
Address (hexadecimal)
Name
Setting range
Default value
Input module
Wiring selection of output Y0 to Y7
0: Not used
1: Safety double wiring (Source/
Source)
2: Safety single
0: Not used
Output module
0180H to 0187H
I/O combined module
0180H to 0187H
Module
Address (hexadecimal)
Name
Setting range
Default value
Input module
Output dark test execution setting Y0 to
Y7
0: Perform
1: Do not perform
0: Perform
Output module
0190H to 0197H
I/O combined module
0190H to 0197H