6 INSTALLATION AND WIRING
6.2 Installation Environment and Installation Position
39
6
6.2
Installation Environment and Installation Position
Installation environment
Installation location
Do not install the safety remote I/O module in a location where:
• Ambient temperature is outside the range of 0 to 55
;
• Ambient humidity is outside the range from 5 to 95% RH;
• Condensation occurs due to rapid temperature change;
• Corrosive gas or combustible gas is present;
• There is a lot of conductive powder such as dust and iron powder, oil mist, salinity, or organic solvent;
• The safety remote I/O module is exposed to direct sunlight;
• A strong electric field or strong magnetic field is generated (
Page 150 Immunity requirements); and
• The safety remote I/O module is subject to vibration and shocks (
Page 18 General Specifications).
Installation surface
Install the safety remote I/O module on the flat surface. When the installation surface is uneven, excessive force is applied to
the printed-circuit board and may cause a defect.
Installation position
When installing the safety remote I/O module on a control panel, provide clearance of 60mm or more (1) between the module
and the sides of any neighboring structures or parts to ensure good ventilation and allow easy safety remote I/O module
replacement.
When installing two or more safety remote I/O modules next to each other, they can be installed in contact with each other.
(1)
(1)
(1)
(1)