66
7 SETTINGS
7.3 Safety Communication Setting
3.
Select "Local Network" in "Communication Destination", and the "Select the target module for the Safety Communication
Setting" window is displayed. Select the target safety remote I/O module and click the [Add] button.
4.
The parameters of the safety remote I/O module selected on the "Select the target module for the Safety Communication
Setting" window are imported into the safety communication setting. Set "Sending Interval Monitoring Time", "Safety
Refresh Monitoring Time", and "Safety Data Transfer Device Setting" and click the [OK] button.
• For the setting values of "Transmission Interval Monitoring Time" and "Safety Refresh Monitoring Time",
refer to the following.
Page 143 Parameter data per station
User's manual for the master station used
• For "Safety authentication code", set the same value as the "Safety authentication code" set in the
parameters of the safety remote I/O module.
• No restrictions are provided on the access level for writing parameters to the safety remote I/O module.
However, when the access level is "Users", even if parameters have been set to the safety remote I/O
module, safety communications are disabled because the safety communication setting cannot be set in the
CPU module. To perform the safety communications, set "Developers" or a higher access level. For details
on the access levels, refer to the following.
GX Works3 Operating Manual