8 FUNCTIONS
8.4 Safety Output
75
8
8.4
Safety Output
This function safely outputs signals. This function cannot be used in any modes other than the safety drive mode. All the
safety remote outputs (SA\Y) are off in any modes other than the safety drive mode.
Safety output wiring selection function
The safety double wiring function or safety single wiring function can be selected for output wiring.
Safety double wiring function
The safety double wiring function supports double outputs.
■
Combination for double wiring
Use the following combinations of output terminals for double wiring to the safety remote I/O module.
Safety single wiring function
This function can connect output devices with single wiring.
(1) External power supply
(2) Safety remote I/O module
(3) Load
Combination of output terminals
Y0, Y1
Y2, Y3
Y4, Y5
Y6, Y7
(1) External power supply
(2) Safety remote I/O module
(3) Load
MC
MC
Y1
Y0
COM-
IO24G
IO24V
(3)
(3)
(1)
(2)
MC
Y0
COM-
IO24G
IO24V
(3)
(1)
(2)